Content |
|
|
| |
Introduction |
 |
 |
|
| |
| The GC-200 Series has been developed to cover the large market for simple temperature-controllers without
unnecessary tools. Nevertheless the controller is provided with a very very quick
microprocessor and auto tuning. This controller is ideal for uncomplicated and clearly
laid out controlled distances. Besides the necessary sary CE-certification they have also
the UL & CSA certification. The GC series combines easy operation with a very good
cost-effectiveness. |
| |
"GC-200 Simple is Best" |
| |
7.1 GC-200 control elements |
 |
 |
|
| |
The slogan "simple is best" fits perfectly on the new GC-200 Series.
» only essential functions
» switchable inputs K, J, E, PT100
» switchable alarm-function
» on / off switch on controller front
» PID and PD characteristic with auto tuning
|
| |
| sensor-testing |
| Thermocouple |
K |
J |
E |
PT100 (1) |
PT100 (2) |
| range min. |
0 °C |
0 °C |
0 °C |
-199 °C |
-19,9 °C |
| range max. |
999 °C |
999 °C |
600 °C |
400 °C |
+99,9 °C |
|
| |
| Thermocouple by IEC-Norm 584; PT100 IEC 751. |
| |
special Features
» new improvement of the controller-algorithmus with special consideration of the heat-up process
» highest measuring precision because of a new analog/frequent-system
» microprocessor circle-time of 250 ms
» safety: this series fulfils the current EMV- and UL regulatons
|
| |
Functions
» sensor and alarmtypus free eligible
» control action selectable
» control output on / off
» sensor-testing
» sensor input correction
» self-diagnostics
» automatic cold junction temperature compensation
» scale for min and max. setting value
|
| |
7.2 FC-100 control elements |
 |
 |
|
| |
The new FC-Series combines high technology and easy
operation. By using this self-adjusting PID-controller the user needs no previous
knowledge of automatic control technology. The use of Fuzzy Logic takes care of optimal
controlled systems.
The modern FC-Series can be delivered in 3 different sizes: |
| |
|
|
| |
With multi additional options as: serial communication RS-232C and RS-485,
analog output, heater burnout alarm, 7 step program setting value.
For FCR and FCD additional with 3 and 4 alarm-output, external setting value, external switch for automatic and power-controll.
At all FC-controllers you can program a temperature leading ramp in ° C/min. and 1 to 4 alarms as absolute or deviation or frequency band
alarm with delay time.
The measure input can be switched between 10 different thermocouples, 2 PT100 resistors, linear voltages and current-signals. |
| |
| Standard specifications |
| Type |
GCS 23 |
GCR 23 |
GCD 23 |
FCS 13 |
FCS 23 |
FCR 13 |
FCD 13 |
| Size (mm) |
48 x 48 x 100 |
48 x 96 x 110 |
96 x 96 x 110 |
48 x 48 x 100 |
48 x 48 x 100 |
48 x 96 x 110 |
96 x 96 x 110 |
| Supply voltage |
100 - 240 V / 50 Hz / 60 Hz; 24 AC/DC by order; |
| Control output |
R = ungrounded relay intern 3A; S = Non-contact for SS-Relay drive; A = analog-relay 4 - 20 mA |
| Control action |
On / Off; PD; PID; Autotuning 2.) |
On / Off; PD; PID; Autotuning 2.); Fuzzy |
| Display |
2 x 3-digit; digital |
2 x 4-digit; digital |
| Input sampling period |
250 ms |
125 ms |
| Accuracy |
+/- 0,3%; +/- 1 Digit of full scale |
| Heating up function |
No |
Yes (vaiabel); Ramp up, down |
| Sensor mistake alarm |
Yes |
| Power output stage by sensor braking |
No |
Option |
| Loop break |
Option |
| max alarm channel |
2 |
4 |
| Serial communication terminals RS 232/485 |
No |
Option |
| Power output stage |
No |
Yes |
| Heating and cooling control |
No |
Option |
No |
Option |
| Program control (7 steps of program) |
No |
Yes |
| Extern switch for program control |
No |
Yes |
| Extern setting value |
No |
Option |
| AUTO/MAN changing |
No |
Option |
|
Legend: 1.) Other specifications on customer request 2.) Autotuning switchable |
| |
7.3 Industrial controller |
 |
 |
|
| |
|
| |
Special features
- » as two step, three step or steady-state controller available
- » easy PID control parameter adjustment by automatic pre- and self alignment
- » simplest control setting by arrow keys
- » configurable universal inputs for thermocouples, PT100 thermometers or freely scalable analogue input (current/ voltage)
- » 3 outputs, switching or continuously for regulation, as linear output for measured or set value or as alarm output
- » two-line luminous LED-display
- » permanent display of set and actual value
- » 2 linkable software alarms which can be assigned to the outputs
- » 3 types of alarm; process alarm, discrepancy alarm, band alarm
- » adjustalbe digital input filter
- » 2 externally switchable setting values
- » comfortably configurable by computer with interface
- » adjustable actual value offset to correct the measured value
- » IP 65 rated
|
| |
Display
- Luminous 2-line LED display (red/ green) for set and actual value 4 LED indicators:
|
 |
SET: |
Controller in parameterizing mode (flashes) |
| AT: |
Autotuning |
| ALM: |
Alarm |
| 1 / 2: |
output 1 resp. 2 is active |
|
| |
| Keys |
 |
- Switch from automatic to manual operation mode in between setting of systematic error (Bias)
Up and down for value adjustment
Funcion key for entering the several programming levels
|
|